CT100 series inverters Product overview
12
multi-step speed setting, PID setting, 485
communication setting
Keep a stable voltage automatically when the
grid voltage transients
Start the rotating motor smoothly
Standard 8-channel inputs, one of which can
be high-speed pulse input (HDI)
Standard 2-channel inputs, AI1: 0 ~ 10V or
4 ~ 20mA input optional, AI2: -10V ~ +10V
input.
Standard 2-channel multi-function collector
outputs, one of which can be high-speed
pulse output (HDO).
Standard 2-channel outputs AO1, AO2 (0 ~
10V or 4~20mA optional)
Standard 2-channel relay outputs
RS485 communication interface for external
RS485 communication,
Modbus protocol (RTU mode)
ACC overcurrent, DEC overcurrent, constant speed overcurrent,
ACC overvoltage, DEC overvoltage, constant speed overvoltage,
bus under voltage, motor overload, inverter overload, input power
failure, output phase loss, rectifier module overheating, inverter
module overheating, external fault, communication fault, current
detection fault, etc.
Highlight LED digital tube displays the
inverter information
Indoors, less than 1km above sea level,
without dust, corrosive gases or direct
sunlight
-10 ~ +40℃, derate 1% for every additional
1℃ when the ambient temperature is
between 40~50℃
0 ~ 2000m, derate 1% for every additional
100m when the sea level is above 1000m