dormakaba ED900 Installation Instructions – Double egress door Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Safety sensor test
-
Safety sensor parameter ST must be set to sensors used and if they are active-high
or active-low. See E safety sensor test error, Appendix B.
Sensor test off.
Sensor test on swing (hinge) side. Active-high
Sensor test on swing and approach sides. Active-high
Sensor test on swing and approach sides. Active-high
Sensor test on swing side. Active-low
ST
Sensor test on approach side. Active-low
Sensor test on swing and approach sides. Active-low
Wall mounted sensor with data line. Lock monitoring not available.
Sensor test overhead sensor type Bodyguard III or Premier T with monitoring input.
Activation by safety sensor on approach
(opposite hinge) side
-
Safety sensor's input is disregarded as soon as door is closed.
Safety sensor can trigger an opening pulse while door is closed.
Suppression of safety sensor on swing
(hinge) side during initialization drive
-
Safety sensor on swing side is active during an initialization drive after a power on
reset.
. With SP set to , operator will disregard swing side safety sensor during
initialization drive. After a power on reset, operator starts an initialization drive
at slow speed. The initialization drive cannot be completed if safety sensor on
hinge side is, or has been triggered.
Delayed opening time for locking
mechanism
. Delayed opening time delay starts as soon as door opening pulse has been generated.
. Door opens on expiration of time delay.
. If parameter is set to "" and input for locking feedback contact is closed, door will not
perform a preload Pu before door unlocks.
. Since various motor locks do not have feedback contacts, a delay of up to seconds is
possible
-
*
ms
*
A.. Driving parameters detail.