EasyManua.ls Logo

Dräger P3U - Page 13

Dräger P3U
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Electrical connections
The maximum possible cable lengths can be found in the table on page 18. In
each case, use the line marked "Number of transmitters = 1".
Connect shielding to earth point and/or 0 V (Ex i).
Installing the transmitters in explosion-hazard areas of zone 2 or 22 without a
safety barrier
Use only supply units of the device category 3.
Take care that the maximum permissible capacitance and inductance of connec-
tions to the supply unit are not exceeded, also taking the cable into account.
The safety-related input parameters of the transmitter are:
C
i
= 5 nF, L
i
= 50 μH.
The maximum possible cable lengths can be found in the table on page 19. In this
table, select the line, " Number of transmitters = 1".
Installing the transmitters in non-explosion-hazard areas:
The maximum possible cable lengths can be found in the table on page 19. In this
table, select the line, " Number of transmitters = 1".
Caution:
The category 1 marking has to be cut out from the rating-plate label. Once the
unit has been used after installation in the above manner, it may never
be installed in explosion-hazard areas of zone 0 or zone 1 (device category 1
or 2). Explosion hazard!
Caution:
The explosion-protection markings has to be removed from the transmitter.
Once the transmitter has been used after installation in this manner, it may
never be installed in explosion-hazard areas.
00923758_1_en .eps
Non-explosion-hazard areaExplosion-hazard area, zone 0, 1 or Div. 1
Safety barrier
Control unit
Ex i
PA
Earth point
4 ... 20 mA
0 V
+
+
4 to 20 mA
+24 V
00823758_1_en.eps
Non-explosion-hazard area
without a safety barrier
Control unit
4 ... 20 mA
0 V
+
+
4 to 20 mA
+24 V
Explosion-hazard area, zone 2 or non-explosion hazard

Table of Contents

Related product manuals