Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 105
The UPS removes power to the parallel UPS system output.
The output relays open, the UPSs transfer to Standby mode, and the
indicators turn off.
4. Switch all UPS battery circuit breakers to the OFF (O) position.
5. If optional EBMs are installed, switch all EBM battery circuit breakers to the OFF (O) position.
6. Switch each UPS input circuit breaker to the OFF (O) position.
7. Switch off utility power where the parallel system is connected.
55..1144 TTrraannssffeerrrriinngg BBeettwweeeenn MMooddeess
From Normal to Bypass Mode. Press any button to activate the menu options, then select CONTROL and
GO TO BYPASS MODE.
From Bypass to Normal Mode. Press any button to activate the menu options, then select CONTROL and GO
TO NORMAL MODE. Alternatively (standalone UPS only): Press any button to activate the menu options, then
select TURN UPS ON/OFF, TURN UPS ON, and OK to confirm.
55..1155 SSeettttiinngg PPoowweerr SSttrraatteeggyy
To set the power strategy:
1. Press any button to activate the menu options, then select SETTINGS, USER SETTINGS, and POWER
STRATEGY.
2. Select HIGH EFFICIENCY or STANDARD, and OK to confirm.
55..1166 CCoonnffiigguurriinngg BBaatttteerryy SSeettttiinnggss
The following battery settings are available:
Configure the UPS for EBMs
BladeUPS 12i model only. Configure the UPS for customer-supplied external batteries
Set the level for Battery Low alarm
Run automatic battery tests
55..1177 CCoonnffiigguurriinngg TThhee UUPPSS FFoorr EEBBMMss
To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
1. Press any button on the front panel display to activate the menu options, then select SETTINGS, USER
SETTINGS, BATTERY SETUP, and NUMBER OF EBMS.
2. Use the
or buttons to select the number of EBMs according to your UPS configuration.( See Table 14 )
Table 14. EBM Selection for UPS Configurations
UPS Configurations
Selection
UPS only 0 (default)
UPS + 1 EBM
1
Transferring Between Modes