112 Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Figure 77. Optional X-Slot Cards
Relay Interface Card
Modbus Card
Industrial Relay Card
Power
Xpert Gateway UPS Card
Power Xpert Gateway
PXGX UPS
EMP Upstream Downstream
100100 Act Act Setup
Restart
Status
DHCP
Ident
Power
66..66 CCoonnttrrooll TTeerrmmiinnaallss
Connect the cables to the control terminals with a mating connector. Input and output terminals have a
functional isolation from terminal to terminal. They are connected to the UPS through individual 1 MΩ resistors.
Figure 78. External Control Terminal Connections
+ Polarity
– Polarity
2
1
+ Polarity
– Polarity
2
1
2
1
2
1
Signal Input 1(
programmable)
Signal Input 2(programmable)
REPO Normally Open
REPO Normally Closed
Normally Open
Normally Closed
1
2
Common
3
Relay Output
UPS
Connectors
(see
Figure 73)
+ Polarity
– Polarity
2
1
Redundant Signal Wiring
(For Parallel Use Only)
+ Polarity
– Polarity
2
1
Standalone/Parallel
NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or
other mechanical control is preferred.
66..77 RReellaayy OOuuttppuutt CCoonnttaaccttss
The UPS incorporates a programmable relay output with potential free contacts for remote alarm indications
(see Figure 78 ). You can obtain an additional four relay outputs with the X-Slot compatible Relay Interface Card.
CAUTION
The relay output contacts must not be connected to any utility connected circuits; the utility requires reinforced
insulation. The relay output contacts have a maximum rating of 30 Vac/1A and 60 Vdc/2A nominal values.
Control Terminals