Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 85
NOTE The load connector breaker controls the load connector only, not the output power cord.
4. Unpack the Powerware Hot Sync CAN Bridge Card and verify that the card was not damaged during
shipment. ( See Figure 67 )
5. If there is a Jumper J7 on the Powerware Hot Sync CAN Bridge Card, remove and discard . See Figure 70 .
NOTE Eaton recommends installing the Powerware Hot Sync CAN Bridge Card in X-
Slot Communication Bay 2 , leaving the X-Slot Communication Bay 1 available for other
types of X-Slot cards.
6. Remove the X-Slot communication bay cover on the UPS and retain the screws.
7. Install the Powerware Hot Sync CAN Bridge Card into the open X-Slot communication bay #2 on the UPS
rear panel. Reinstall screws and tighten.
8. Retain both blue terminating plugs for future use.
Figure 69. Installing the Blue Terminating Plug (Single Parallel-Ready UPS Installation)
Blue Terminating Plug (CAN OUT)Blue Terminating Plug (CAN IN)
9. Tighten the screws securing the Powerware Hot Sync CAN Bridge Card in its X-Slot communication bay.
Single Parallel Ready UPS Installation