6 Parameters
100 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
P-32 160 rw 0 - 25 s DC-braking 0
Used to define the length of time during which direct current will be
applied to the motor if the output frequency reaches a value of 0.0 Hz.
Note:
The voltage level will be the same as the voltage amplification set in
P-11.
P-33
161 rw Motor pick-up control function (to catch spinning motors) (in sizes FS2
and FS3) / DC braking, braking time at start (in size FS1)
0
If this parameter is enabled, the frequency inverter will attempt to
determine whether the motor is already turning during a start. It will
then start to control the motor starting from the motor's current speed.
A brief deceleration will occur if motors that are not already turning are
started.
Note:
Direct current connection time when starting (FS1-size frequency
inverters only): Used to set the length of time during which a direct
current will be applied to the motor in order to ensure that it will be
stopped if the frequency inverter is activated.
0 Deactivated
1 activated
P-34 162 rw Brake chopper activation (only with sizes FS2 and FS3) 0
0 locked
1 Enabled with overload protection braking resistance
2 Enabled without overload protection braking resistance
P-35 163 rw Analog input 1 scaling 100
0 - 500 %
Used to scale the analog input by this factor.
Example: For P-16 and a 0 -10 V signal and a scaling factor of 200.0 %,
a 5 V input will make the frequency inverter run at the maximum
frequency / speed (P-01).
P-36
164 rw Serial communication configuration
This parameter has three settings that are used to configure serial
Modbus RTU communications.
These subparameters are as follows:
0 - 63 Frequency inverter slave address 1
Baud rate OP-buS
1 OP-buS
2 9.6 kBit/s
3 19.2 Kbit/s
4 38.4 kBit/s
5 57.6 kBit/s
6 115.2 kBit/s
TimedOut 3000 ms
locked, 30 - 3000 ms
PNU ID Access rights Value Description DS
RUN ro/rw