6 Parameters
6.3 Operational data indicator
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 137
P-00 - Display values
P00-01 20 ro % Analog input 1
100 % = Maximum input voltage
P00-02 21 ro % Analog input 2
100 % = Maximum input voltage
P00-03 23 ro Hz/rpm Frequency reference value / Motor shaft speed
Shown in Hz if P-10 = 0;
otherwise shown in rpm
P00-04 11 ro State
DI1, DI2, DI3,
DI4
Digital inputs 1 - 4
State of the frequency inverter's digital input
P00-05 ro 0 reserved
P00-06 ro 0 reserved
P00-07 ro V Motor voltage: the value of the rms voltage being applied at the motor
P00-08 23 ro V Internal DC bus voltage
P00-09 24 ro °C Unit Temperature
Heatsink temperature in °C
P00-10 ro HH:MM:SS The frequency inverter's operating time
Not affected when the parameters are reset to their default settings.
P00-11 ro HH:MM:SS The frequency inverter's operating time since the last trip (1)
Operating time clock stopped by frequency inverter lockup (or trip). Reset
with next enable only if a trip occurred. Also reset with next enable after
the frequency inverter's mains power is switched off.
P00-12 ro HH:MM:SS The frequency inverter's operating time since the last trip (2)
Operating time clock stopped by frequency inverter lockup (or trip). Reset
with next enable only if a trip occurred (undervoltage does not count as a
trip) – Not reset when mains power is switched off/on unless a trip
occurred before the mains power was switched off.
P00-13 ro HH:MM:SS The frequency inverters operating time since the last lockup
The frequency inverters operating time clock was stopped with the
lockup. Reset the value with next enable.
P00-14 ro 4 - 32 kHz Pulse frequency
The frequency inverters actual rms output pulse frequency. If the
frequency inverter is too hot, this value may be lower than the frequency
selected in P-17. The frequency inverter will automatically reduce the
pulse frequency in order to prevent an excess temperature trip and main-
tain operation.
P00-15 ro 0 - 1000 V DC bus voltage log (256 ms)
The eight most recent values before the trip
Updated every 250 ms.
P00-16 ro -20 - 120 °C Log for thermistor temperature
The eight most recent values before the trip
Updated every 500 ms.
PNU ID Access rights Value Description DS