10/10 MN05003003Z-EN
Technical data
101
Relay switching frequency
Mechanical switch operations Switch
operations
10 mill. (107)
Mechanical switching frequency Hz
10
Resistive lamp load Hz
2
Inductive load Hz
0.5
Transistor outputs
Number of outputs 8
Rated voltage U
e
V DC
24
Permissible range V DC
20.4 bis 28.8
Residual ripple %
F 5
Supply current
On 0 state, typical/maximum mA 18/32
On 1 state, typical/maximum mA
24/44
Reverse polarity protection
hCaution!
Connecting the outputs to a power supply with a reverse polarity will result
in a short-circuit.
Yes
Potential isolation
Yes
Rated current I
e
at state 1, maximum A
0.5
Lamp load without R
V
W
5
Residual current on signal 0 per channel mA
< 0.1
Maximum output voltage
On “0” signal with external load, 10 MO V 2.5
On „1“, signal, I
e
= 0.5 A
U = Ue – 1 V
Short-circuit protection (thermal) Group Q1 to Q4 /Group
Q5 to Q8. Evaluation with
Diagnostics input I16 (Q1 to Q4), I17 (Q5 to Q8)
hCaution!
Set the output group in the program to a “0” signal
in order to prevent the output from overloading
Yes
Short-circuit tripping current for R
a
F 10 mO
(depending on number of active channels and their
load)
A
0.7 F I
e
F 2
Maximum total short-circuit current A 16
Peak short-circuit current A
32
Thermal cutout
Yes
Maximum switching frequency with constant resistive
load R
L
= 100 kO (depends on program and load)
Switch
operations/h
40000

Table of Contents