10 Product specifications
10.1 Model numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS
systems are available in 50/60 Hz with various output power ratings.
The following sections detail the input, output, environmental, and battery specifications for the UPS.
10.2 Single module specifications
10.2.1 UPS system input
10.2.2 UPS system output
Models Power Rating Frequency
9395P 500 kVA 500 kVA PF 1.0 50/60 Hz
9395P 600 kVA 600 kVA PF 0.92 50/60 Hz
Operating Input Voltage
(Nominal + ā15%)
400 Vac for operation from 340 Vac to 460 Vac
Operating Input Frequency Range
±5 Hz
Operating Input Current
See Table 3-4 on page 19 and Table 3-5.
Reduced for Generator Adjustable
Input Current Harmonic Content
< 3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 61000-4-5
Battery Voltage
480 Vdc
UPS Output Capacity 100% rated current
Output Voltage Regulation ±10% dynamic, ±1.5% steady state
Output Voltage Adjustment (Nominal +/ā3%) 380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac
Output Voltage Harmonic Content 1.5% max THD (linear load)
5% max THD (nonlinear load)
Output Current See Table 3-4 on page 19.