Loading...
P-164000476 9395P 500kVA / 600 kVA 86
Revision 002 User’s and Installation Guide
Table 7-1:Status Indicators
7.3.2 Using the Touch Screen
The touch screen control panel provides an operator interface with the UPS system. The figure below
identifies the display areas discussed in the following sections.
Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right
corner of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password
request pop-up (see Figure ā€œSign In or Password Request Screenā€).
Figure 7-4. Parts of the Touch Screen
A The UPS status area automatically displays the Eaton model number, current time and date, active
alarms, active notices, and load percent and battery run time for the UPS. If the Environmental
Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
Indicator Status Descriptions
Green
Lit
Steady
The UPS is in Online mode, operating normally. The power module is supplying power to the
critical load.
Yellow
Lit
Steady
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the
Online indicator also remains illuminated.
Yellow
Lit
Steady
The UPS is in Bypass mode. The critical load is supported by the bypass source. The Online
indicator is not illuminated when the system is in Bypass mode.
Red
Lit
Steady
The UPS has an active alarm and requires immediate attention. The screen shows the highest
priority active alarms. All alarms are accompanied by an audible horn. To silence the horn,
press any control panel pushbutton once. The Alarm indicator may be illuminated along with
other indicators.
Lit
Flashing
There is a new UPS alarm condition. The indicator flashes until acknowledged by pressing
anywhere on the control panel once.