P-164000476 9395P 500kVA / 600 kVA 58
Revision 002 User’s and Installation Guide
Table 5-2: CAN Bridge Card wiring terminations
Figure 5-5. Distributed bypass Pull-Chain wiring without MOBs
NOTE
Use twisted pair wiring between the UPS and MOB AUX contacts.
Table 5-3: Pull-Chain wiring terminations
J3-10 (Shield) J3-10 (Shield) J3-10 (Shield) J3-10 (Shield)
From UPS 1 To UPS 2 To UPS 3 (if installed) To UPS 4 (if installed)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)
TB2-1
(Pull Chain)
TB2-2
(Pull Chain)
TB2-2
(Pull Chain)
TB2-2
(Pull Chain)
TB2-2
(Pull Chain)