Revision 002 Userās and Installation Guide
6.3 UPS system oneline configurations
The system oneline drawings in this section show the simplified internal structure of the UPS, battery
supply, and basic maintenance bypass.
If the load requires a neutral, a bypass source neutral must be provided. If the load does not
require a neutral and there is no neutral conductor connected at the bypass input, a neutral
must be installed to source star point.
Callout letters A, B, C, and D map to Table 3-4 on page 19.
Oneline drawing UPS model
Voltage
System type
Input Output
Figure 6-6 on
page 69
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Two UPM, Common Rec-
tifier Feed, Common Battery, Dual-Feed
Configuration
Figure 6-7 on
page 70
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Two UPM, Common Rec-
tifier Feed, Separate Battery, Dual-Feed
Configuration
Figure 6-8 on
page 71
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Three UPM, Common
Rectifier Feed, Common Battery, Dual-Feed
Configuration
Figure 6-9 on
page 72
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Three UPM, Common
Rectifier Feed, Separate Battery, Dual-Feed
Configuration
Figure 6-6 on
page 69
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Two UPM, Common Rec-
tifier Feed, Common Battery, IOM Configuration
Figure 6-7 on
page 70
9395P-600 kVA
9395P-500 kVA
400 400 Single Reverse Transfer UPS - Two UPM, Common Rec-
tifier Feed, Separate Battery, IOM Configuration
Figure 6-10 on
page 73
9395P-600 kVA
9395P-500 kVA
400 400 Simplified Dual-Feed UPS with Maintenance Bypass
Panel