EasyManua.ls Logo

Eaton Power Xpert 9395P - Page 56

Eaton Power Xpert 9395P
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P-164000476 9395P 500kVA / 600 kVA 46
Revision 002 User’s and Installation Guide
NOTE
All building alarm inputs require an isolated normally-open or normally-closed contact or switch
(rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as
shown. Building alarm inputs can be programmed for use with either normally-open or
normally-closed contacts. All control wiring and relay and switch contacts are customer-
supplied.
The building alarms can be programmed to display the alarm functional name.
A jumper wire must be connected between pins 1 and 2 on TB1 if the normally-closed remote EPO
contact is not used.
Terminal TB1 Name Description
1 Remote EPO NC
Dry contact used to activate remote EPO of UPS.
2 Remote EPO return
3 Remote EPO NO
4 Remote EPO return
5 Battery aux
6 Battery aux return
7 48 Vdc battery shunt trip +
8 48 Vdc battery shunt trip -
9K3 AUX
10 K3 AUX return
Terminal TB2 Name Description
1 Pull chain
Backup control for parallel operation.
2 Pull chain return
3 Alarm relay NC
General purpose normally-open (NO) and normally-closed (NC)
relay contacts.
4 Alarm relay return
5 Alarm relay NO
6 Alarm relay return
7 Not used
8 Not used
9 Not used
10 Not used
Terminal TB3 Name Description
1 Building alarm 1
Programmable UPS alarm. Activated by a remote dry contact clo-
sure.
2 Building alarm 1 return
3 Building alarm 2
Programmable UPS alarm. Activated by a remote dry contact clo-
sure.
4 Building alarm 2 return

Table of Contents

Other manuals for Eaton Power Xpert 9395P

Related product manuals