5 Fault messages
5.1 Introduction
140 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
E-trip 11 External fault (at digital input 5, terminal 10, if P1-13 = 6/7/16/17). There must
be a high-level signal at this input in order to be able to run the variable
frequency drive.
If a thermistor is connected to terminal 10, check whether the motor is too
hot.
SC-ObS
12 Communication fault with an external operating unit or with a PC.
Check connections.
F
(t-dc 13 Excessively high DC link voltage ripple
The DC link voltage ripple can be viewed using P0-16.
P0-37 contains a fault register with the last values before the unit was
switched off (scan time: 20 ms).
Check to make sure that all the mains supply phases are present and that
their voltage balance falls within the permissible tolerance range (3%).
Reduce the load if possible.
If the fault persists, please contact your nearest Eaton sales branch.
P-LOss
14 Incoming power phase failure (only for devices with a three-phase power
supply)
h O-I
15 Overcurrent at output
See Error no. 03.
th-f
(t 16 Malfunctioning heat sink thermistor.
Please contact your nearest Eaton sales branch.
dAtA-F
17 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
4-20 F
18 The analog input’s input current does not fall within the specified range.
Check the setting in P2-30 for AI1 (terminal 6) and P2-33 for AI2
(terminal 10).
In the case of 4-20 mA: Check the setpoint connection for wire breakage.
dAtA-E
19 Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
Change the parameter values (again) and save them once more.
If the message appears again, please contact your nearest Eaton sales
branch.
V-dEf
20 The customer’s settings for the parameters have been imported.
Press the STOP button.
F-Ptc
21 Motor PTC thermistor over temperature
FAn-F
22 The device’s internal fan is experiencing a fault
In the case of frame size FS8: Wrong device fan operating direction
Check the supply voltage phase sequence (L1–L2–L3).
O-hEAt 23 The measured ambient temperature exceeds the specified value.
Check the device’s internal fan.
Make sure that the required clearance around the device is being
maintained and that cooling air can flow through the vents on the device
unimpeded.
Reduce the switching frequency with P2-24.
If possible: Reduce the load.
O-torq
24 Maximum permissible torque exceeded.
If possible: Reduce the load or increase acceleration time t-acc.
V-torq
25 Only active if brake control is enabled in hoisting gear mode (P2-18 = 8). The
torque produced before the hoisting gear’s mechanical brake is enabled falls
below the set threshold.
Message
Error no.
[dec]
Possible causes and fixes