5 Fault messages
5.1 Introduction
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com 141
OVt-F 26 Device output fault
Please contact your nearest Eaton sales branch.
Sto-F
29 Internal STO circuit fault
Please contact your nearest Eaton sales branch.
Enc-01
30 No communication between the encoder module and the variable frequency
drive.
Check to make sure that the module is correctly plugged in and secured.
Enc-02
SP-Err
31 The calculated motor speed is different from the measured motor speed.
Check the encoder connection, including the corresponding shielding.
Increase the value of P6-07 if necessary.
Enc-03 32 The motor speed and the PPR value entered in P6-06 do not match. The PPR
value in P6-06 must be at least 60.
Check the speed entered in P1-10.
Enc-04 33 Channel A fault:
Usually a bad connection.
Check wiring.
Enc-05
34 Channel B fault
Usually a bad connection.
Check wiring.
Enc-06 35 Error on channels A and B
Usually a bad connection.
Check wiring.
AtF-01 40 Motor identification failed:
The measured stator resistance varies between the phases.
Make sure that the motor is connected properly and working correctly.
Check the motor windings to make sure they have the same resistance
values.
AtF-02
41 Motor identification failed:
The measured stator resistance is too large.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
AtF-03 42 Motor identification failed:
The measured motor inductance is too low.
Make sure that the motor is connected properly and working correctly.
AtF-04
43 Motor identification failed:
The measured motor inductance is too high.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
AtF-05 44 Motor identification failed:
The measured motor parameters do not match.
Make sure that the motor is connected properly and working correctly.
Check to make sure that the device’s rated output matches the motor’s
rated output. The difference should not exceed one full output class.
OVt-Ph
49 A phase in the motor cable is not connected or has a discontinuity.
Sc-FO1 50 No valid Modbus frame was received within the time specified in P5-06.
Check to make sure that the network master is working correctly.
Check connecting cables.
Increase the value of P5-06 to an acceptable value.
Message
Error no.
[dec]
Possible causes and fixes