3 Installation
3.3 Mount ing
78 DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
Table 6: Installation dimensions, screws, tightening torques
3.3.3.2 Fixing on a mounting rail
As an alternative to screw fixing, DA1 variable frequency drives (sizes FS2
and FS3) and a degree of protection of IP20 can also be mounted on a
mounting rail as per IEC/EN 60715.
Figure 43:Mounting rail conforming with IEC/EN 60715
Frame size
Degree of
protection
a1 b1 Screw Tightening torque
FS
IP NEMA mm Occur in mm Occur in Quantity Size N/m lb-in
FS2 IP20 NEMA 0 75 2.95 215 8.46 4 M4 1 8.85
FS2
IP66 NEMA 4X 176 6.93 200 7.87 4 M4 1.2 - 1.5 10.62 - 13.27
FS3 IP20 NEMA 0 100 3.94 255 10.04 4 M4 1 8.85
FS3 IP66 NEMA 4X 198 7.78 252 9.9 4 M4 1.2 - 1.5 10.62 - 13.27
FS4 IP55 NEMA 12 110 4.33 428 16.85 4 M8 4 35.4
FS5
IP55 NEMA 12 175 6.89 515 20.28 4 M8 15 132.76
FS6
IP55 NEMA 12 200 7.87 840 33.07 4 M10 20 177
FS7 IP55 NEMA 12 200 7.87 1255 44.41 4 M10 20 177
FS8 IP20 NEMA 0 420 16.54 942 37.09 4 M12 57 504.5
1 in = 1’’ = 25.4 mm; 1 mm = 0.0394 in
If you use EMC mounting adapters (DX-EMC-MNT-…), use a tall
mounting rail (15 mm) preferably.