PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Below is various defined control word (STW1) command.
Table 109. Control word (STW1) message examples
SN
Control
word
(STW1) Control word description (STW1) Comment
1 0x0400 Set PLC Control PLC Control should be set in MCU
2 0x0000 Clear PLC Control PLC Control should be reset in MCU
3 0x040F Run Command without RFG Motor Off as no RAMP Generator
4 0x0407 Clear Run Command Motor Off as earlier
5 0x041F Run Command with RFG and without Set point Motor Off as no Set point Generator
6 0x0407 Clear Run Command Motor Off as earlier
7 0x047F Run Command with RFG and with Set point Motor ON with RFG
8 0x0407 Clear Run Command Motor Off as earlier
9 0x047F Run Command with RFG and with Set point Motor ON with RFG
10 0x045F Set Freeze of Ramp Motor ON with Ramp Freeze
11 0x047F Clear Freeze of Ramp Motor ON with Following Ramp Timing
12 0x047E OFF 1 Command Motor Off with RFG
13 0x047F Run Command with RFG and with Set point Motor ON with RFG
14 0x047D OFF 2 Command (Coast Stop) Motor Off with Coast
15 0x047F Run Command with RFG and with Set point Motor ON with RFG
16 0x047B OFF 3 Command (Quick Stop) Motor Off with 0 DECEL Time
17 0x047F Run Command with RFG and with Set point Motor ON with RFG
18 0x0477 Disable Operation Motor Off with Coast
19 0x057F Run Command with RFG and with Set point At Jog Speed Motor ON at Jog Speed
20 0x0477 Disable Operation Motor Off with Coast
21 0x0480 Fault Reset bit Fault should get reset
Status word 1 (ZSW1)
Table 110. Application status word PROFIdrive
Bit Value Significance Comments
0 1 Ready To Switch On Power supply is switched on, electronics initialized, main contact, if available, has dropped out,
pulses are inhibited.
0 Not Ready To Switch On
1 1 Ready To Operate Refer to control word 1, bit 0.
0 Not Ready To Operate
2 1 Operation Enabled Drive follows set point. This means, that the electronic and pulses are enabled (Refer to control
word 1, bit 3), the closed loop control is active and controls the motor and the output of the set point
channel is the input for the closed loop control.
0 Operation Disabled Either the pulses are disabled or the drive doesn’t follow the output value of the set point channel.
3 1 Fault Present Unacknowledged faults or currently not acknowledgeable faults (fault messages) are present (in the
fault buffer). The fault reaction is fault-specific and device-specific. The acknowledging of a fault may
only be successful, if the fault cause has disappeared or has been removed before. If the fault has
isolated the voltage, the drive goes into the “Switching On Inhibited” condition, otherwise the drive
returns to operation. The related fault numbers are in the fault buffer.
0 No Fault
4 1 Coast Stop Not Activated
(No OFF 2)
0 Coast Stop Activated (OFF 2) “Coast Stop (OFF 2)” command is present.