5
Option Card Slots
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
EMC directive
For the electrical equipment installed in the EMC, directive
states that the equipment must not disturb the environment
and must be immune to other electromagnetic disturbances
in the environment. Table 3 indicates the requirements for
the control wiring to meet this directive.
Table 3. Control wiring requirements
Item Directive
Product
IEC 61800-2
Safety
UL 508C, IEC / EN 61800-5-1
EMC (at default
settings)
Immunity: EN / IEC 61800-3, 2nd environment
Radiated emissions: EN / IEC 61800-3 (Transient Testing
included), 1st environment
Conducted emissions: EN / IEC 61800-3
Category C1: is possible with external filter connected to
drive. Please consult factory
Category C2: with internal filter maximum of 10m motor
cablelength (FR0: This is obtained with 2 turns on a ferrite
core and using metal ground plate)
Category C3: with internal filter maximum of 50m motor
cable length (FR0: This is obtained with no ferrite core and
metal plate)
Control cable grounding
It is recommended that the shielded cables be grounded
as shown in Figure 6. Strip the cable insulation required
allowing attachment to the frame with the grounding clamp.
Figure 6. Control cable grounding
Table 4. PowerXL Series—drive option boards
DX H –NET
–
PROFB
Function
PROFB = PROFIBUS
DEVICENET = DeviceNet
CANopen = CANopen
SWD-IP20 = SmartWire IP20
Series
H = HVAC purpose
Type
NET = Communication card
EXT = I/O card
ACC = Accessory
SPR = Spare part
KEY = Keypad
CBL = Cable
Basic naming
DX = PowerXL Drive
SWD-IP54 = SmartWire IP54
Table 5. PowerXL Series drives protocols
Protocols
PowerXL Series Drives
On Board/Option ModuleDG1 DH1
Modbus RTU
■■
On Board
BACnet MSTP
■■
On Board
EtherNet/IP
■
— On Board
Modbus TCP
■■
On Board
PROFIBUS
■■
Option Module
CANopen
■
—Option Module
DeviceNET
■
—Option Module
SmartWire-DT
■
—Option Module
BACnet IP —
■
On Board