Commissioning
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Figure 71. DH1 keypad navigation to ethernet comm settings
BYPASS J OG
13: 53
M: Moni t or
P: Pa r a met er
F: Faul t
P2: I nput s
BYPASS REVERSE
13: 53
P13: Syst em
Right/OK key
Do wn Ke y t o
Co mmuni cat i ons
P13: Syst em
BYPASS
REVERSE
13: 53
STP FWD KEY PAR
P12: Communi cat i on
P11: Real Ti me Cl ock
REVERSEBYPASS 1 3 : 5 3
STP
FWD KEY PAR
P12. 4: Et her Net Bus
P12. 1: Pr ocess Dat a I nput Sel
P12. 2: Pr ocess Dat a Out put Sel
P1: Ba s i c
STP FWD KEY TPM
STP FWD KEY PAR
Right/OK key
REVERSE
P12. 1: FB Pr ocess Dat a I nput
BYPASS 1 3 : 5 3
STP
FWD KEY PAR
P12. 3: RS485 Bus
P12. 4: Et her Net Bus
Do wn Ke y t o Et h e r Ne t Bu s
BYPASS REVERSE13: 53
STP FWD KEY PAR
P12. 4. 1: Basi c Set t i ng
P12. 4. 2: Modbus TCP
Right/OK key
In this menu you will be able to scroll through the below settings to setup the communication protocol.
Table 197. EtherNet/IP
DH1 code Parameter Min. Max. Unit Default ID Note
P12.4.1.1
IP Address Mode 1 1500 0 = Static IP
1 = DHCP with AutoIP
P12.4.1.2
Active IP Address 1507
P12.4.1.3
Active Subnet Mask 1509
P12.4.1.4
Active Default Gateway 1511
P12.4.1.5
MAC Address 1513
P12.4.1.6
Static IP Address 192.168.1.254 1501
P12.4.1.7
Static Subnet Mask 255.255.255.0 1503
P12.4.1.8
Static Default Gateway 192.168.1.1 1505
P12.4.1.9
Enable BACnet IP 01 017250 = Disable
1 = Enable
ote: N BACnet/IP uses parameters from EtherNet/IP.