EtherNet/IP On-Board Communications
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Control supervisor object, class 0x29
Table 72. Control supervisor object
ID Description Data type Access rule Default Range
Class Attributes
01h Revision UINT Get 1 —
02h Max instance UINT Get 1 —
03h Number of instances UINT Get 1 —
Class Services
0Eh Get_attribute_single
Instance Attributes
03h Run1 (RunForward) BOOL Get/Set 0 0–1
04h Run2 (RunReverse) BOOL Get/Set 0 0–1
05h NetCtrl BOOL Get/Set 0 0–1
06h State USINT Get 0 0–7
07h Running1 BOOL Get 0 0–1
08h Running2 BOOL Get 0 0–1
09h Ready BOOL Get 0 0–1
0Ah Faulted BOOL Get 0 0–1
0Bh Warning BOOL Get 0 0–1
0Ch FaultRst BOOL Get/Set 0 0–1
0Fh CtrlFromNet BOOL Get 0 0–1
0Dh Active fault code
UINT Get 0 0–65535
6Ch Comm idle action value BOOL Get/Set 2 0–2
6Dh Comm timeout UINT Get/Set 10 sec 0-60sec
Instance Services
0Eh Get_attribute_single
10h Set_attribute_single
05h Reset (Type 0) Type 0
See Appendix C for list of Fault Codes.
ote: N When both Run (Run1 & Run2) attributes set, then no action.