Assembly instance 107
Table 162. Instance 107 (Input) length = 8 bytes
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1 Drive State
/
process data
selector value
2 % Speed Actual (Low Byte)
3 % Speed Actual (High Byte)
4 Process DataOut1 (Low Byte)
5 Process DataOut1 (High Byte)
6 Process DataOut2 (Low Byte)
7 Process DataOut2 (High Byte)
Refer “State transition diagram,” provided under “Control Supervisor Object” and
“Drive State” table specified at end of “Input Instances” section.
Drive State
0x00 DN_NON_EXISTANT
0x01 DN_STARTUP
0x02 DN_NOT_READY
0x03 DN_READY
0x04 DN_ENABLED
0x05 DN_STOPPING
0x06 DN_FAULT_STOP
0x07 DN_FAULTED
Speed Actual. This is the actual value from the frequency converter. The value is between
0 and 10000. In the application, the value is scaled in percentage of frequency area between
set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
ote: N See info on Assembly 101 for varying values in the Process Data Out 1 and Process Data Out 2 Bytes.
See Appendix B on default Process Data info.