19
Modbus TCP On-Board communications
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Figure 16. DH1 keypad navigation to ethernet comm settings
In this menu you will be able to scroll through the below settings to setup the communication protocol.
Table 34. EtherNet/IP / Modbus TCP—P20.3
DG1 code DH1 code Parameter Min. Max. Unit Default ID Note
P20.4.1 P12.4.1.1
IP Address Mode 1 1500 0 = Static IP
1 = DHCP with AutoIP
P20.4.2 P12.4.1.2
Active IP Address 1507
P20.4.3 P12.4.1.3
Active Subnet Mask 1509
P20.4.4 P12.4.1.4
Active Default Gateway 1511
P20.4.5 P12.4.1.5
MAC Address 1513
P20.4.6 P12.4.1.6
Static IP Address 192.168.1.254 1501
P20.4.7 P12.4.1.7
Static Subnet Mask 255.255.255.0 1503
P20.4.8 P12.4.1.8
Static Default Gateway 192.168.1.1 1505
—P12.4.1.9
Enable BACnet IP01 017250 = Disable
1 = Enable