129
Hardware specifi cation
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Assembly instance 111
Table 157. Instance 111 (Output) length = 20 bytes
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 NetRef NetCtrl FB Input Data 2 FB Input Data 1 FaultReset Direction Run
1NA
2 FBSpeedReference (Low Byte)
3 FBSpeedReference (High Byte)
4 ProcessDataIn1 (LowByte)
5ProcessDataIn1 (HighByte)
6 ProcessDataIn2 (LowByte)
7ProcessDataIn2 (HighByte)
8 ProcessDataIn3 (LowByte)
9ProcessDataIn3 (HighByte)
10 ProcessDataIn4 (LowByte)
11 ProcessDataIn4 (HighByte)
12 ProcessDataIn5 (LowByte)
13 ProcessDataIn5 (HighByte)
14 ProcessDataIn6 (LowByte)
15 ProcessDataIn6 (HighByte)
16 ProcessDataIn7 (LowByte)
17 ProcessDataIn7 (HighByte)
18 ProcessDataIn8 (LowByte)
19 ProcessDataIn8 (HighByte)
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0 to 10000.
In the application, the value is scaled in percentage of the frequency area between set minimum and maximum
frequency. (0 = 0.00%–10000 = 100.00%).