223
Appendix B—Process Data Values
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
When configuring the Process Data parameters for the drive, there are many parameters which can monitored over the
fieldbus and selected using the communications settings group menu items.
Menu Item Parameter Parameter Number
Default Monitored
Parameter
P20.1.1 FB Data Out 1 Sel 1 Output Frequency
P20.1.2 FB Data Out 2 Sel 2 Motor Speed
P20.1.3 FB Data Out 3 Sel 3 Motor Current
P20.1.4 FB Data Out 4 Sel 4 Motor Torque
P20.1.5 FB Data Out 5 Sel 5 Motor Power
P20.1.6 FB Data Out 6 Sel 6 Motor Voltage
P20.1.7 FB Data Out 7 Sel 7 DC-link Voltage
P20.1.8 FB Data Out 8 Sel 8 Unit Temperature
However, since these Menu Items are read write items, these monitored parameters can be modified to any parameter in
the drive by simply changing the value for the menu item. For example, if in FB Data Out 8 one wanted to monitor the state
of the Digital Inputs D1 to D3 they would change Process Data Out 8 from an 8 to a 12. For a complete list of parameters
please refer to Communication Application Guide which can be found on the drives web site.
Typically the parameters which are monitored over fieldbus are the same types of parameters monitored on the Monitoring
menu of the drive, a list of those parameters andIDs are provided below.
Parameter ID Description Parameter ID Description
1 Output Frequency 16 PID1 Set Point
2 Motor Speed 18 PID1 Feedback
3 Motor Current 20 PID1 Error Value
4 Motor Torque 22 PID1 Output
5 Motor Power 23 PID1 Status
6 Motor Voltage 24 Freq Reference
7 DC-link Voltage 25 Analog Output 1
8 Unit Temperature 26 Running Motors
9 Motor Temperature 27 PT100 Temperature
10 Analog Input 1 28 Last Active Fault
11 Analog Input 2 30 Multi-Monitoring
12 DI1, DI2, DI3 32 PID2 Set Point
13 DI4, DI5, DI6 34 PID2 Feedback
14 DO1 36 PID2 Error Value
15 Torque Reference 38 PID2 Output
39 PID2 Status