Version 2.02 15.05.2007 Function of VS 3000
30
Basic time and maximum variable time for switching forward (on) and back (off) are definable as parameters for each
loading/unloading of a condenser stage. The following relationships apply for determining control times:
t = t
b
+ t
v
t
b
= Definable
The following applies for t
v
:
t
v
= t
v_max
−
t
v_max
⋅ d
t
d
t_max
The following applies:
d
t
>d
t_max
d
t
=d
t_max
t
v
= Variable control time
t
v_max
= Max. control time (definable for each stage)
d
t
= Control error
d
t_max
= Max. control error (definable)
Control time is calculated at every controller run. The variable time is calculated anew and the time elapsed
since the last control time is compared w ith the calculated time. If the calculated control time is smaller than or
equal to the elapsed time, fan actuation takes place w hen the control error is greater than the specified neutral
zone.
The following diagram shows calculation of the control time:
ZNR. 51203 65 330 E0
Control error dt [°C]
Run time [s]
VS 3000 Condenser fan run times
0
2
4
6
dt
8
10
dt max
12
0
20
40
60
80
100
120
140
120
160
180
200
220
240
t
v max
Basic time t
b
Run time t = t + t
b
t+t
v maxbv
t
b
t
v
When high pressure is controlled by step controller, the number of fan stages running is output via the Fan
Speed analog output according to the following equation:
U
OFF
=
(
No of compressor stages running ⋅ 10V
)
(
No of compressor stages defined
)