Version 2.02 15.05.2007
Menu Structure of VS 3000
113
eckelmann.de
E 2007 - ECKELMANN AG | BERLINER STRASSE 161 | 65205 WIESBADEN | TELEFON + 49(0)611 71 03-0 | FAX +49(0)611 71 03-133
8.1.8 Men u 7 Default settin g s
VS3000 POS: XXXXX Entry
Load defaukt?
Are you sure?
NO: ESC Yes: ↵
Prompt to confirm loading of default parameters ↵, ESC
8.1.9 M en u 8 Service Mode
SERVICE POS: XXXXX
1 Analog values Move to Menu 8-1
2 Compressor Move to Menu 8-2
3 Condenser fan Move to Menu 8-3
4 System Move to Menu 8-4
5 D2D Move to Menu 8-5
S Menu 8-1 Default Analog Values
SERVICE POS: XXXXX Entry
Default / Dimension
NT LT Dim.
AnalogOut1 X.X V Voltage at Analog Output 1 (terminals 53,54) ↑, ↓
0,0..10,0
0,0 0,0 V
AnalogOut2 X.X V Voltage at Analog Output 2 (terminals 55,56) ↑, ↓
0,0..10,0
0,0 0,0 V
AnalogOut3 X.XX V Voltage at Analog Output 3 (terminals 57,58) ↑, ↓
0,00..10,00
0,00 0,00 V
S Menu 8-2 Default Compressor ON/OFF
SERVICE POS: XXXXX Entry
Default / Dimension
NT LT Dim.
Comp. C 1 XXX
Control status of res
ective com
ressor
sta
e
↑, ↓
(ON/OFF)
OFF OFF -
...
ON or OFF
Onl
the actual number of com
ressors
Comp. C 12 XXX
(stages) is shown.
↑, ↓
(ON/OFF)
OFF OFF -
VS 3000 basic module: Compressor (Stage) 1 - max. 4
With 1st SIOX extension module: Compressor (S t age) 1 - max. 8
With 2nd SIOX extension module: Compressor (Stage) 1 - max. 12