Version 2.02 15.05.2007 Alarms and Messages of VS 3000
118
9.3.2 System fault alarms
In occurrence of a HP Measuring Loop Error, condenser stages are unloaded when compressors are stationary
and loaded when compressors are running. Capacity stages are likewise loaded when compressors have been
started manually. Actuation takes place after the basic time has elapsed. No allowance is made for variable
times.
In occurrence of an LP Measuring Loop Error, compressor capacity stages are loaded or unloaded until about
50% of all available compressor capacity stages are working. Actuation takes place after the basic time has
elapsed. No allowance is made for variable times. In occurrence of all other Measuring Loop Errors, computa-
tion continues with the most recent valid value for the duration of the error.
EPROM and RAM errors are fatal errors and result in the controller going on HOLD, as correct running of the
program can then no longer be expected. Output signals are reset.
No. Message System fault reported
1 Meas.err.cylTemp Cx Error in measuring loop to detect cylinder head temperature of
Compressor Cx
2 Meas. error HP Error in measuring loop to detect high pressure
3 Meas. error LP Error in measuring loop to detect low pressure
4 Meas. error tr Error in measuring loop to detect room temperature
5 Meas. error tod FError in measuring loop to detect outside temperature
6 Meas.err.humid Error in measuring loop to detect air humidity
7 RTC error Fault in controller real-time clock
8 EEPROM error Fault in internal EEPROM (parameter memory)
9 RAM error Fault in internal data memory
10 SIOX error x Failure of SIOX extension module No. x
11 Battery voltage Internal battery fault