EasyManuals Logo

ECKELMANN VS 3000 User Manual

Default Icon
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Version 2.02 15.05.2007
Function of VS 3000
5
eckelmann.de
E 2007 - ECKELMANN AG | BERLINER STRASSE 161 | 65205 WIESBADEN | TELEFON +49(0)611 71 03-0 | FAX +49(0)611 71 03-133
3.1 System configuration
The VS 3000 Pack Controller contains a low-pressure control loop (LP, compressor control) and a high-pressure
control loop (HP, condenser control). Two different temperature ranges are provided for compressor control (NT:
normal-temperature refrigeration or LT: low-temperature refrigeration; see also Section 2 - Application).
Compressor control largely covers the following control and regulating functions:
Low-pressure control (LP, compressor control) for single-circuit systems - step or combined control
S Load shedding
S Emergency power mode
S Base load rotation
S Compressor monitoring
S Safety loop
S D2D two-pipe discharge gas defrosting
High-pressure control (HP, condenser control) for single-circuit systems - step or speed control
3.2 Low-pressure control / Compressor control
S Step controller
- Control by loading and unloading compressor stages or compressor capacity stages
S Combined controller
- Control by variable-speed compressor in combination with one or more fixed-speed compressors
The setpoint is defined as a function of room (ambient) temperature. Actual values are detected by a pressure
transducer with continuous current output (4 to 20 mA) or voltage output (0 to 10 V).
3 Function of VS 3000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ECKELMANN VS 3000 and is the answer not in the manual?

ECKELMANN VS 3000 Specifications

General IconGeneral
BrandECKELMANN
ModelVS 3000
CategoryController
LanguageEnglish

Related product manuals