Version 2.02 15.05.2007 Menu Structure of VS 3000
106
Messages POS: XXXXX Entry Default / Dimension
NT LT Dim.
Meas. error tod X Outdoor temperature measuring loop error -, 0..2 2 2 -
Meas. error tr X Room temperature measuring loop error -, 0..2 2 2 -
Meas.err.hunid. X Humidity sensor measuring loop error -, 0..2 2 2 -
Power failure X S tart following power failure -, 0..2 0 0 -
First start X Controller start -, 0..2 2 2 -
Burst disc X Bursting disk input actuated -, 0..2 - - -
External alarm X External alarm input actuated -, 0..2 - 2 -
I/O module error X SIOX I/O module failure -, 0..2 1 1 -
Service mode X Service mode activated -, 0..2 0 0 -
Comp/cond unload X External unload activated -, 0..2 0 0 -
Load shed X Compressor disabled by load shedding -, 0..2 0 0 -
Low liq. level X Low liquid level cutout tripped -, 0..2 2 2 -
RAM error X Internal data memory fault -, 0..2 1 1 -
EEPROM error X EEPROM (parameter memory) fault -, 0..2 2 2 -
RTC error X Real-time clock fault -, 0..2 2 2 -
Setpoint changed X Setpoint changed -, 0..2 0 0 -
Max. speed F X Threshold value for speed adjuster exceeded. -, 0..2 0 0 -
Battery voltage X Internal battery fault -, 0..2 2 2 -
Manual OFF X Compressor OFF by manual switch -, 0..2 0 0 -
Manual ON X Compressor ON by manual switch -, 0..2 0 0 -
Emerg. working X Emergency operating mode - , 0..2 0 0 -
HP cutout D2D Z1 X High-pressure cutout for discharge gas defrosting
Z1 cases
-, 0..2 2 2 -
HP cutout D2D Z2 X High-pressure cutout for discharge gas defrosting
Z2 cases
-, 0..2 2 2 -
HPcutout D2D Z2R X High-pressure cutout for discharge gas defrosting
Zs coldrooms
-, 0..2 2 2 -
Disable D2D Z1 X Disable discharge gas defrosting Z1 -, 0..2 0 0 -
Disable D2D Z2 X Disable discharge gas defrosting Z2 -, 0..2 0 0 -
Disable D2D Z2R X Disable discharge gas defrosting Z2 coldrooms -, 0..2 0 0 -
Fault D2D Z1 X Discharge gas defrosting fault Z1 -, 0..2 2 2 -
Fault D2D Z2 X Discharge gas defrosting fault Z2 -, 0..2 2 2 -
Fault D2D Z2R X Discharge gas defrosting fault Z2 coldrooms -, 0..2 2 2 -
Sens type change X Sensor matching changed -, 0..2 0 0 -
Comp auto disabl X Automatic compressor disable - , 0..2 2 2 -
too many starts/h X Compressor short-cycling (LP combined control-
ler)
-, 0..2 2 2 -
no load level X No load level received (t0 shift) -, 0..2 2 2 -