Version 2.02 15.05.2007
Alarms and Messages of VS 3000
117
eckelmann.de
E 2007 - ECKELMANN AG | BERLINER STRASSE 161 | 65205 WIESBADEN | TELEFON +49(0)611 71 03-0 | FAX +49(0)611 71 03-133
No. Message Process fault reported
26 HD-Begr. D2D Z2Z Digital input for high-pressure cutout with discharge gas defro-
sting of Z2 coldrooms is active
27 Disable D2D Z1 Digital input for disabling discharge gas defrosting of Z1 cases
is active (not yet implemented)
28 Disable D2D Z2 Digital input for disabling discharge gas defrosting of Z2 cases
is active
29 HD-Begr. D2D Z1 Digital input for disabling discharge gas defrosting of Z2 col-
drooms is active
30 Fault D2D Z1 Fault in discharge gas defrosting of Z1 cases (not yet imple-
mented
31 HD-Begr. D2D Z2 Fault in discharge gas defrosting of Z2 cases
32 HD-Begr. D2D Z2R Fault in discharge gas defrosting of Z2 coldrooms
33 Sens type change Parameter for matching pressure transducers has been chan-
ged
34 Comp auto disabl Compressor Stage x automatically disabled (high cylinder
head temperature 5 times in one day)
35 too many starts/h Compressor short cycling with compressor combined control
36 no load level No load level information for refrigeration points received with
t
0
shift
37 NT Cascade 1 NT Cascade 1 not available or fault condition
38 NT Cascade 2 NT Cascade 2 not available or fault condition

Table of Contents