1 Menu 1 - Alarms and messages
Tappingthisbuttonopensthealarmlistscreen;thisdoesnotshowanyentriesthen.The"Current
Alarms" view is displayed as default. Use the left "Message List" "tab" button to change to the message list. The
message list contains all messages and current alarms with the priority 0..99 that have been listed by the
system centre from connected E*LDS components system-wide and the activated external alarms signalled via
the digital inputs.
IfanyE*LDScomponentsignalsanalarm,thebuttoninthemainmenuchangestored.Tappingthis
button opens the alarm list screen in which the current alarms or alarms that can be acknowledged are now
listed.
The current alarms (only priority 1..99) are shown in the alarm list until they are signalled as rectified and have
been acknowledged by the operator.
Thissymbolmustbeconfirmedfortheacknowledgementoftherectifiedalarms.Acknowledged
alarms are automatically moved into the message list, forming the history of the alarms that have occurred in
the installation.
The screen contains the following information
Incoming:Dateandtimeofalarmsandmessagesastheyoccurred(receivetimestamp).
Outgoing - in the alarm list:Ifanyredalarmsymbolcanbeseeninthiscolumn,thismeansthatalarmswith
the priority 1..9 are still pending, the faults have not yet been rectified and these alarms cannot be
acknowledged! On the other hand, if there is a date and time in this column, the problems or causes of the
alarm have been rectified and the alarm has gone and can be acknowledged using the acknowledge button in
the right area. These alarms are then removed from the alarm list; however they are always still in the message
list.