6 System Centre Installation and Start-up
6.1 Installation
Specified mounting position:
ATTENTION
Important safety information! Before the installation and start-up, chapter Safety Information must be
read carefully in its entirety and all safety instructions and hazard warnings must be observed. Any
maintenance by the user is not intended as possible hazards from incorrect re-assembly cannot be
ruled out. Opening the device is not authorised! Furthermore, it must be noted that the safety of the
system or the installation in which the device is integrated is the responsibility of the creator of the
system or installation. If the device is used in any way not specified by Eckelmann AG, the protection
supported by the device can be compromised!
The user must be logged in at the system centre, see chapter Login to the system centre (unlocking),
to be able to make changes to the system centre or to E*LDS components.
ATTENTION
Important safety information! The controller is exclusively intended for installation in a switch
cabinet! The specified mounting position is:
The controller must be mounted with the "Logo" and the lettering "ECKELMANN" facing upwards.
The natural convection of the circulating air with free air exchange is sufficient to prevent overheating
for the operation of the controller. A sufficiently large air inlet (min. 100 mm) under the device and an
unobstructed air outlet above it must always be ensured. If this cannot be guaranteed, forced
ventilation is required!