8 Menu 2-8 - Special Inputs
Thedigitalspecialinputsofthesystemcentrearecalledupusingthisbutton.Allimportant
parameters and the status of the inputs are displayed there.
following special inputs are available:
shunt lock
emergency power supply
sprinkler alarm
storelighting
setpointtoggle
The screen contains the following parameters:
Special inputs
Shunt lock Predefined designation of the special input (digital input)
PriorityXX Priority of the signal / alarm input
Delay time [sec.] XX Delay time of the signal / alarm in seconds
Quiescent current (low-active) X Alarmissignalledif
- quiescent current = Yes: (signal voltage not present low-active)
- quiescent current = No: (signal voltage is present high-active)
Input X
Connectionoftheinput
1)
Status XX Current status of the input: OK = light grey, no signalling Waiting = yellow:
signalling, delay time running, Message = green: no alarm Alarm = red: signalling,
alarm / message has been tripped
1)
Designationsofthesupportedmodules/inputs:
CI 4x00system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX11.extensionmodule,inputs1..12
SIOX22.extensionmodule,inputs1..12
SIOX33.extensionmodule,inputs1..12
SIOX44.extensionmodule,inputs1..12
DDC1 1. GLT DDC module 1
DDC2 2. GLT DDC module 2
DDC3 3. GLT DDC module 3
DDC4 4. GLT DDC module 4
Note: GLT = building control and DDC = Digital Direct Control
As the display for all special inputs is identical, the explanations are provided using the example of the
“shuntlock”.
The digital special inputs are configured using Menu 4-1-3. Detailed description of the functions can be
found in chapters Digitale Eingänge.