Special days
Up to 30 special days on which the Service Centre is not manned can be defined using this entry screen. New
special days are defined using the button for editing.
The screen contains the following parameters:
Special days alarm signalling Entry Default
Entry screen for date The input is made as follows: D/M or DD/MM
(day/month)
A special day can be deleted / removed again
with the entry of
"--" or "0:0" or "00:00".
1/1 ..31/12
--,0:0, 00:00
-
Provider
Thetelephoneproviders(e.g.D2,EPlus,…)fortheSMSdestinationsaredefinedusingthisentryscreen.
The screen contains the following parameters:
Alarm signalling provider 1/2 Entry Default
Description Description of the provider 1/2 e.g. "D2" Max. 19 characters -
Telephone number Telephone number of the provider 1/2 -
Protocol SMS protocol of the provider 1/2
NOTE: This must be requested from the
provider!
TAP, UCP TAP
If no days are specified, the Service Centre is considered as always manned!
An alternative destination with a different telephone number and a different provider should always be
used for every destination! It is not ensured after successful transmission of any message to the
provider that this reaches the recipient promptly or at all. For this reason, alarm signalling only by SMS
should not be used and another separate alarm path should be implemented.