5. Again, assuming you want to preserve your existing wiring to
the terminal blocks, because you haven’t wired to the terminal
blocks on the replacement module, remove the terminal block
board and terminal housing assembly from the new replacement
module.
6. Carefully slide the new module into the same I/O slot in the
housing and tighten the top and bottom capture fasteners, but not
too tight.
Figure 5-9. New I/O Module in Place Prior to Attaching Terminal Board and Terminal Housing
Assembly
7. Take the terminal block board and terminal housing assembly,
with all the I/O wiring, that you removed in step 4, and line up
its fasteners with the holes on the module, now seated in the
housing, and gently push the terminal block board and terminal
housing assembly into the module and tighten the fasteners.
8. When the new board starts, and is functioning properly, return
any processes you put into manual control to automatic control.