Table 6-3: Troubleshooting chart (continued)
Symptom Possible cause Action
Configuration of FCU 2160 Check the communication address specified for
the Rosemount 2410 in the FCU Slave Database.
Check configuration of communication
parameters for the FCU Fieldbus ports.
Check that the correct communication channel
is selected.
See the Rosemount Tank Gauging System
Configuration Manual (Document No.
00809-0300-5100) for more information on how to
configure the FCU 2160.
Configuration of communication
protocol
In TankMaster WinSetup/Protocol Channel
Properties:
check that the protocol channel is enabled
check the protocol channel configuration (port,
parameters, modem).
No contact with the
Rosemount 2410 Tank
Hub
Hardware failure Check the Rosemount 2410 Tank Hub; check
the Error LED or the integral display for
information.
Check the 2460 System Hub (or 2160 Field
Communication Unit).
Check the Field Bus Modem.
Check the communication port on the control
room PC.
Check that all devices connected to the Primary/
Secondary bus are powered.
Contact Emerson Automation Solutions/
Rosemount Tank Gauging service department.
Software failure
Restart the Rosemount 2410 by disconnecting
and connecting the power supply (note the
communication parameters that appear on the
display during startup).
Service and troubleshooting Reference Manual
December 2019 00809-0100-2410
100 Reference Manual