6.2 Service
This section briefly describes functions which may be useful for service and maintenance
of a Rosemount 2410 Tank Hub. If not otherwise stated, most examples are based on
using the TankMaster WinSetup tool to access these functions. The Rosemount Tank
Gauging System Configuration Manual (Document No. 00809-0300-5100) provides more
information on how to use the TankMaster WinSetup program.
6.2.1 Viewing input and holding registers using TankMaster
™
In a Rosemount Tank Gauging system, measurement data is continuously stored in Input
Registers of devices such as the Rosemount 2410 Tank Hub, Rosemount 5900 Radar Level
Gauge, and others. By viewing the input registers of a device, you can verify that the
device is working properly.
Holding Registers store various device parameters used to control measurement
performance.
Procedure
1. Start the TankMaster WinSetup program.
2. In the TankMaster WinSetup workspace window, select the device icon.
3. Right-click and select View Input/View Holding Registers option, or from the
Service menu choose Devices → View Input/View Holding Registers.
Now the View Input/Holding Register window appears.
4. In the Registers Type list, select Predefined or All.
Option
Description
Predefined View a basic selection of registers.
All View a range of registers by your own choice (for
advanced service).
5. For the All option, you have to specify a range of registers by setting a start value in
the Start Register input field, and the total number of registers to be displayed in
the Number of Registers field (1-500). Up to 50 registers is recommended for a
quick update of the list.
Service and troubleshooting Reference Manual
December 2019 00809-0100-2410
80 Reference Manual