C.3 Change the communication parameters for the
primary bus
The Rosemount 2410 has a Primary Bus which is used for communication with a
Rosemount 2460 System Hub. It may also be connected directly to a control room PC. The
Primary Bus supports TRL2, RS485, and other communication buses. The Rosemount 2410
automatically detects what modem is installed in the Primary Bus slot and communication
parameters are set accordingly. For some modem types (such as RS485) the non standard
option allows you to configure communication with other protocols than the standard
Modbus
®
.
Procedure
1. Open the Primary Bus window.
a) In the TankMaster WinSetup workspace, right-click the Rosemount 2410 Tank
Hub icon.
b) Choose the Properties option.
The 2410 Tank Hub window appears.
c) Select the Configuration tab.
d) Click the Primary Bus button.
The Primary Bus Configuration window lets you configure protocol, baudrate,
and other communication parameters when the standard settings are not
appropriate.
2. To change communication parameters:
a) In the Configuration drop-down menu, change from Standard to Non
Standard.
b) Choose the desired Protocol.
c) Choose appropriate communication parameter values for Baudrate,
Databits, Parity, and Stop Bits.
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 161