C.6 Set up a Rosemount 2410 for hybrid density
applications
The Rosemount TankMaster software can be used in a hybrid density system to calculate
Observed Density. Density calculations are also available for a host system connected
directly to a Rosemount 2410 without using TankMaster. Then the density calculations are
performed internally by the Rosemount 2410 Tank Hub.
Procedure
1. Install and connect the devices on the tank including the Vapor Pressure sensor (P3)
and the Liquid Pressure sensor (P1).
2. Start the TankMaster Winsetup configuration program.
3. Configure the Rosemount 2410 Tank Hub
(15)
. Ensure that the appropriate devices
are associated with the current tank in the Rosemount 2410 tank database as
illustrated below.
Example
In the example below a Rosemount 5900S Radar Level Gauge, a Rosemount 2240S
Multi-input Temperature Transmitter, and two Rosemount 3051S Pressure
Transmitters (P1 and P3) are installed on the tank.
4. Configure the Rosemount 5900S Radar Level Gauge
(15)
.
5. Configure the Auxiliary Tank Devices
(15)
(Rosemount 2240S Multi-input
Temperature Transmitter).
(15)
See the Rosemount Tank Gauging System Configuration Manual (Document no. 00809-0300-5100) for more information.
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 167