6. In the 22XX ATD/Advanced Parameter Source Configuration window, ensure that the
Vapor Pressure (P3) and Liquid Pressure (P1) parameters are mapped to the actual
source devices on the tank as shown below.
In case there is no vapor pressure sensor installed, a manual value can be used
instead.
7. Configure the Hybrid Density function, see Hybrid density configuration.
8. Configure the tank as described in the Rosemount Tank Gauging System
Configuration Manual.
C.6.1
Hybrid density configuration
To configure the hybrid density function do the following:
Procedure
1. In the TankMaster WinSetup workspace, right-click the Rosemount 2410 icon.
2. Choose the Properties option.
The 2410 Tank Hub window appears.
3. Select the Configuration tab.
4. Click the Hybrid Density No. [X] button to open the 2410 Tank Hub Hybrid Density
Configuration window. Up to three tanks can be configured for Hybrid Density
calculations.
Advanced configuration Reference Manual
December 2019 00809-0100-2410
168 Reference Manual