6. The Registers Scope drop-down list has three options:
Scope Description Access level
Basic Standard setting that includes the most
commonly used registers
View Only
Service Includes a wider range of registers for
advanced service and troubleshooting
Supervisor
Developer For advanced users only Administrator
7. In the Show Values in pane, choose the appropriate register format Decimal or
Hexadecimal.
8. Click the Read button.
Now the View Input/Holding Registers window is updated with the current register
values.
6.2.2
Editing holding registers using TankMaster
™
Most Holding Registers can be edited simply by typing a new value in the appropriate
Value input field. Some Holding Registers (marked grey in the Value column) can be
edited in a separate window. In this case you can choose from a list of options or you can
change separate data bits.
For more information see the Rosemount Tank Gauging System Configuration Manual
(Document No. 00809-0300-5100).
6.2.3
View the device live list in TankMaster
™
The Device Live List lets you view devices connected to the Tankbus. You can, for
example, see Device Id, Tag, and whether the devices are configured or not.
The Device Live List is useful when you are going to configure devices in a Rosemount
Tank Gauging system, in order to verify that the required devices are connected to the
Tankbus.
Procedure
1. Start the TankMaster WinSetup program.
2. In the TankMaster WinSetup workspace, select the Rosemount 2410 icon.
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 81