Power budget
Table A-4: Power Consumption for Various Rosemount Tank Gauging Devices
Field device Power consumption
Rosemount 5900S Radar Level Gauge 50 mA
Rosemount 5900C Radar Level Gauge 50 mA
Rosemount 5900S Radar Level Gauge, 2-in-1
solution
100 mA
Rosemount 5300 Level Transmitter 21 mA
Rosemount 5408 Level Transmitter 21 mA
Rosemount 2230 Graphical Field Display 30 mA
Rosemount 2240S Multi-input Temperature
Transmitter
30 mA including 565, 566 and 765 temperature
sensors
Rosemount 644 Temperature Transmitter 12 mA
Rosemount 3051S, and Rosemount 2051
Pressure Transmitters
18 mA
Allowed cabling distances
Figure A-9: Cable Distances
D
C
B A
D
D
C
C
B
B
A
A
The total cable distance A+B+C+D must not exceed the values given in Table A-5.
Reference Manual Specifications and reference data
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 125