Procedure
1. In the TankMaster WinSetup workspace, right-click the Rosemount 2410 icon.
2. Choose the Properties option.
The 2410 Tank Hub window appears.
3. Select the Configuration tab.
4. Click one of the Virtual Relay No. buttons.
C.5.1 Using two/three relay zones
You may use two or three relay zones. Different relay states can be used in each of these
zones.
With two relay zones, use one set point: First Point.
With three relay zones, use two set points: First Point and Second Point.
C.5.2
First and second set points
The first and second set points define the transitions between Zone 1, 2 and 3. You can set
different relay states in each of these zones.
First Point defines the transition between Zone 1 and 2.
Second Point defines the transition between Zone 2 and 3.
C.5.3
Hysteresis
When the source variable passes a set point, the relay switches from one state to the
other. When the source signal returns back into the previous zone, the relay does not
switch back to the previous state until it has passed both the set point and the hysteresis
zone.
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 163