Table C-4: Holding Registers for Volume Configuration (continued)
Name Holding Register Description
Volume offset 4318 Strapping table volume offset. Use this function
to include product volume below the zero level.
This offset will be added to the calculated
volume.
Note
The Volume Offset is added when predefined
tank shapes are used as well.
Volume unit 4320 40: Us Gallons
41: Liter
42: UK Gallons
43: Cubic Meter
46: Barrels
112: Cubic Feet
Tank no.
(The Rosemount 2410
tank database shows
which devices are
mapped to the different
tanks)
4322 0: not active
1: tank 1
2: tank 2
n: tank n
10: tank 10
Strap table level 0 4334 Level value for strapping table point no. 0
Strap table volume 0 4336 Volume value for strapping table point no. 0
Strap table level 1 4338 Level value for strapping table point no. 1
Strap table volume 1 4340 Volume value for strapping table point no. 1
Strap table level 99 4730 Level value for strapping table point no. 99
Strap table volume 99 4732 Volume value for strapping table point no. 99
The TankMaster WinSetup program lets you edit Holding registers for volume calculations
as illustrated in Figure C-2.
Advanced configuration Reference Manual
December 2019 00809-0100-2410
172 Reference Manual