If no tank name is configured you can check the tank hub’s tank database in case
you need to verify that the selected tank position corresponds to the desired tank.
7. Choose the tank parameter and value unit to associate with the 4 - 20 mA Analog
Output.
8. Under Value Range, set the source values that correspond to the analog output
values 4 mA and 20 mA, respectively.
You can specify any value as long as the 20 mA value is above the 4 mA value. Alarm
mode is activated in case the measurement value goes out of range.
9. In the Alarm Mode list, set the alarm mode as desired.
Alarm mode specifies the analog output state when a measurement error occurs, or
when the measurement value is out of range.
Option Description
High The output current is set to 21.75 mA (default
setting).
Low The output current is set to 3.75 mA (default setting).
Freeze current The output current is set to the present value at the
time when the error occurs.
10. Optional: Click the Advanced button to specify Low/High Alarm Currents and Low/
High Saturation Limits.
The output range for the analog output is 3.5 to 23 mA.
C.9.1
View the current status
The Analog Output Status window displays information on the current status.
Procedure
To view the current status information, click the button to the right of the Status field.
In case an error has occurred the Status field indicates “BAD”:
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 181