EasyManua.ls Logo

Emerson Rosemount 2410 - Page 37

Emerson Rosemount 2410
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 3-2: Installation on One Tank
A. Rosemount 2410 Tank Hub
B. Rosemount 2230 Display
C. Rosemount 5900S Radar Level Gauge
D. Rosemount 2240S Temperature Transmitter
E. Tankbus
F. 300 m
G. Voltage drop=1.4 V
The total operating current of the connected field devices on the tank is 50+30+30
mA=110 mA. This is within the output capability of the Rosemount 2410 Tank Hub.
Calculations
The tank hub is powered by an intrinsically safe power supply: 12.5 V, 250 mA.
Voltage drop to the tank: 110 mA x 0.30 km x 42 Ω/km=1.4 V.
Voltage at the tank =12.5 V - 1.4 V=11.1 V.
Result: the input voltage of 11.1 V to the field devices is above the minimum requirement
of 9 V.
Related information
Power budget
Example 2
The second example, illustrated in Figure 3-3, includes two tanks with a Rosemount 2410
Tank Hub acting as power supply to the field devices on both tanks.
The first tank is located 300 m away from the Rosemount 2410 Tank Hub and the second
tank a further 350 m away.
Both tanks have two field devices: a Rosemount 5408 Radar Level Transmitter and a
Rosemount 644 Temperature Transmitter. The total current consumption of the two
devices is 32 mA (see Table 3-2).
Reference Manual Installation
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 37

Table of Contents

Other manuals for Emerson Rosemount 2410

Related product manuals