Optional secondary bus
In addition to the Tankbus an optional intrinsically safe bus is available for communication
with devices not compatible with FOUNDATION
Fieldbus. It allows you to connect devices
for intrinsically safe HART 4-20 mA analog input/output communication.
IS terminal block for SIL safety systems
For Safety Integrity Level (SIL) systems the Rosemount 2410 has a terminal block with a SIL
Alarm output for connection to a Rosemount 5900S Radar Level Gauge.
Figure 3-21: IS/Exi Terminal Block for SIL Systems
IS/Exi
B
A
A. SIL Alarm
B. Ground screws
Table 3-12: Terminal Assignment for SIL Version of the Rosemount 2410 IS Terminal
Block
Terminal Designation Function
1a FB + Intrinsically Safe Tankbus positive (+) terminal
1b FB + Intrinsically Safe Tankbus positive (+) terminal
2a FB - Intrinsically Safe Tankbus negative (-) terminal
2b FB - Intrinsically Safe Tankbus negative (-) terminal
3 IS I/O+ IS Input/Output +
4 IS I/O - IS Input/Output -
5 Alarm -
SIL Alarm input -
(connect to terminal block on Rosemount 5900S)
6 Alarm +
SIL Alarm input+
(connect to terminal block on Rosemount 5900S)
GND_1 GND_1 Housing chassis/Tankbus shield
GND_2 GND_2 Housing chassis/Tankbus shield
Reference Manual Installation
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 59