©2020 EMS Ltd. All rights reserved. Page 25 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP
Addressable fire system wiring
SKIP THIS STEP IF CONNECTING TO A CONVENTIONAL FIRE SYSTEM.
Wire the inputs as shown below, using the resistor pack provided.
If an input is not being used, leave the 20 kΩ resistor as factory fitted.
Both outputs are voltage free and rated 30 V @ 1 A.
The maximum cable length to connected devices is 10 m.
FOOTNOTES
*
†
Optional cabling, required only when the following SmartCell devices are added to the WZM;
detectors, call points and I/O Units (I/O units when set to ‘Off When Reset’) - see page 30 for details on
this feature.
Wiring can be normally open or normally closed operation as required.
BAT
ENABLE
TAMPER
RESET
AERIAL A AERIAL B
ATTENTION
ELECTROSTATIC
SENSITIVE DEVICE
RS232
EN54-4 UNIVERSAL PSU
SC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
STATUS
FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL
START
INPUT
L N
For additional information refer to TSD042
0359-CPR-00267
15
0905
SLIDE TO
REMOVE
EOL
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)
SOUNDER A
L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT
ZONE
A B
A B NC C NO NC C NO
FIRE
INPUT2
INPUT1
FAULT
FAULT
ACTIVE
FAULT
ACTIVE
A
B
C
D
230 VAC variant shown
NC C NO NC C NO
FIRE
FAULT
A B
INPUT1
FAULT
ACTIVE
A B
INPUT2
FAULT
ACTIVE
FAULT INPUT
FIRE INPUT
NO C
FIRE OUTPUT 2
(to clear when
panel reset)
FIRE OUTPUT 1
(to clear when
panel silenced)
NO C NC NO C
Addressable re system connections
NO C NC
*
††
4k720k
4k7
20k