Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 95
Navigation Setup → Extended setup → Current output → High alarm curr. (052)
Write permission Operators/Service engineers/Expert
Description Enter the current value for maximum alarm current. See also "Output fail mode".
Input range 21 to 23 mA
Factory setting 22 mA
Set min. current (053)
Navigation Setup → Extended setup → Current output → Set min. current (053)
Write permission Operators/Service engineers/Expert
Description Enter lower current limit.
Some switching units accept no current smaller than 4.0 mA.
Options 3.8 mA
4.0 mA
Factory setting 3.8 mA
Output current (054)
Navigation Setup → Extended setup → Current output → Output current (054)
Write permission Operators/Service engineers/Expert
Description Displays the current current value.
Get LRV (015)
Navigation Setup → Extended . setup → Current output → Get LRV (015)
Write permission Operators/Service engineers/Expert
Description Setting lower range value. The pressure for the lower current value (4 mA) is present at
the device. Use the "Confirm" option to assign the lower current value to the applied
pressure value.
Prerequisite Pressure measuring mode
Options Cancel
Confirm